T400 Controller Facilities Manual
667/EB/20200/000 Page 7-3 Issue 9
Stage movements for all red units are specified as follows:
Unit 7 1 - 2
Unit 6 1 - 3
Unit 5 2 - 3
Unit 4 4 - 5
Unit 3 4 - 6
Unit 2 5 - 8
Unit 1 8 - 1
TABLES
321
Units Binary Value 4 Binary Value 2 Binary Value 1
7 1 - 2 1 - 2 1 - 2
6 1 - 3 1 - 3
5 2 - 3 2 - 3
44 - 5
3 4 - 6 4 - 6
25 - 8
18 - 1
As can be seen from above, the stage moves are entered in the appropriate tables to
equate to the required unit. Thus a movement cannot be specified for two units.
In the example in Figure 21.9, all-red detectors AR1 & AR2 are required to extend
stage transitions 1-2, 1-3 and 1-4, while AR3 & AR4 are required on 3-1 & 3-4. An
extension time of 2.0 seconds and a maximum time of 12 seconds are required.
7.2.1 Independent Intergreens
In some circumstances, when a normal Extend All Red (Hold Intergreen) is applied to
an intersection, there are some phases to which the Intergreen Extension applies, which
are not involved in the conflict, and so whose appearance does not need to be delayed.
In order to cater for this requirement, the Independant Intergreen Facility has been
incorporated within the software. It is possible to specify at configuration, for each
terminating phase, the intergreens to the gaining phases which will not be held by the
Extend All Red facility.
7.2.2 Extend All Red (Hold I/G) Parallel Stage Streaming Facilities
There is an extend all red Facility available on each stream. There is a separate All Red
Extension time and All Red Maximum time for each stream. If the extend all red input
is active on the specified stage to stage movement, then when the first phase in the
stream that is about to go to green reaches the start of its red-green transition period,
the intergreen and delay times concerned with the intergreen are held until the All Red
extension period terminates or the All Red Maximum time is reached. (See also section
19.2.)