T400 Controller Facilities Manual
667/EB/20200/000 Page 11-2 Issue 9
If the mains fails for more than 30 days (this threshold is configurable and also
alterable via handset PFD command) then an entry is made in the fault log and the
RTC time is considered invalid. The timetable is then not available and the timetable
settings are set to their default state.
11.3 TIMETABLE RESOLUTION
CLF plans and timetable events are introduced by timetable settings to a resolution of
1 second.
11.4 BRITISH SUMMER TIME CHANGES
The RTC will advance or retard one hour at 02.00 hours on the Sunday morning of
specified weeks to allow for the time changes of British Summer Time.
When the clock is advanced, any CLF plan change or timetable event facility that
would have occurred between 2 a.m. and 3 a.m. will automatically be brought into
effect.
When the clock is retarded, a return to the conditions applicable at 2 a.m. is
automatically implemented.
The programmed week numbers may be changed via the handset using the BSA and
BSR commands.
Note: The advance and retard week numbers are not reset after being actioned and will
be effective the following year unless changed or set to ‘0’ to inhibit the facility.
11.5 MINUTE PULSE
This signal is of 5 seconds duration and begins 5 seconds before each 5 minute
boundary of the RTC. It is available to special conditioning and therefore may be
allocated to a normal T400 output Port bit. Conditioning bit goes active for duration of
pulse.