T400 Controller Facilities Manual
667/EB/20200/000 Page 9-52 Issue 9
CombinationA’ would be used for Stream 0, Influence Set Combination ‘B’ for
Stream 1, etc.
In this way, it is possible on introduction of a group, to operate different influences at
the same time on different streams.
If it is required that, during a given group timing, a stream is not required to change
influence, then this stream’s influence should be set to Group Influence number 7,
followed by the related stage number, i.e. the number of any stage contained within the
stream upon which the influence acts. (See section 9.9.7, Figure 9.7(a).)
Only one plan can be in operation on the controller at once while in CLF. CLF can run
on all streams at once or on some streams with the remainder running higher priority
modes. If CLF is disabled on a stream then that stream will run the next lower priority
mode.
For further description of CLF mode see section 9.8.