T400 Controller Facilities Manual
667/EB/20200/000 Page 19-10 Issue 9
19.3 L.M.U. PARALLEL STAGE STREAMING FACILITIES
19.3.1 LMU Supplementary Intergreen Extensions
There is an LMU supplementary intergreen extension facility available for each stream.
If an LMU indicates one red lamp fail (see Section 19.2) then the all red period of the
intergreens on the configured stage to stage movements will be held until the
supplementary extension timer expires. The extension period is measured from the
stage change point. Each stream’s extension can be accessed by using the handset
command:
SIE followed by the stream number (e.g. SIE 2). Data is in the range 0 to 31.8 seconds
in 0.2 second steps.
19.3.2 LMU Maximum All Red
There is an LMU maximum all red facility available for each stream. If an LMU
indicates a second red lamp failure pending (see section 19.2) then the all red period of
the intergreens on the configured stage to stage movements will be held until the LMU
maximum all red timer expires. The maximum period is measured from the stage
change point. Each stream’s maximum can be accessed by using the handset command:
LMX followed by the stream number (e.g. LMX 0). Data is in the range 0 to 255
seconds in 1 second steps.