T400 Controller Facilities Manual
667/EB/20200/000 Page A-8 Issue 9
Appendix APPENDIX A) .5) Cable Distances for SDE
NOTE: SDE/SA cabling assumes the use of 2 Channel Detectors, some 4 Channel
Detectors can be used for SDE/SA. See Manufacturer’s information.
91m‘n’ m 68m
Stop Line
T400
NB: The following tables for distances assume the use of 1mm
2
cable with the detector
current specified. Use of larger cable will increase the length of run possible as will use
of detectors with a lower operating current. Recalculate any values as required on a
pro-rata basis.
Table APPENDIX A) -13) Cable Distances for SDE using Siemens or Microsense
Detectors
Cable length from stop line to controller = n’ metres
Cable 1mm
2
= 0.0362 Ohm/metre loop
Supply Voltage for Detectors = 19.2V - 28.8V
Detector PSU Output Voltage = 27.5V+4.5% (Max 28.74V, Min
26.26V)
Max permissible volt drop (27.5V PSU) = 7.06V.
Logic PSU = 24v+6% (Max 25.44V, Min 22.56V)
Max permissible volt drop (24V supply) = 3.36V.
Cable Length ‘n’
Power supply: 27.5v P.S.U. 24v P.S.U.
3-lane 1 conductor out & return 37.5 metres UNUSABLE
3-lane 2 conductors out & return 200 metres 29.7 metres
2-lane 1 conductor out & return 48.8 metres UNUSABLE
2-lane 2 conductors out & return 362 metres 107 metres
1-lane 1 conductor out & return 362 metres 107 metres
1-lane 2 conductors out & return 850 metres 339 metres