T400 Controller Facilities Manual
667/EB/20200/000 Page 25-16 Issue 9
25.3 RLM GENERAL DESCRIPTION
25.3.1 Background Information
The RLM facility is required at part-time signals and at junctions which are fitted with
pedestrian audible or tactile devices. The vehicle red lamps are monitored and when
lamp failures are detected, the operation of the controller is modified to ensure that
unsafe signal conditions do not occur.
The RLM function is provided by the T400 firmware operating in conjunction with a
RLM unit. The RLM unit hardware comprises a T400 ancillary processor card
(666/1/02239/001), together with current monitoring transformers (toroids) and a
voltage monitoring transformer. The ancillary processor card resides in the T400
module rack and communicates with the T400 main processor card via the extended
system bus ribbon cable. The T400 can also operate with a free-standing RLM unit,
giving reduced facilities.
This RLM function, which applies to intersection controllers, should not be confused
with Pelican Red Lamp Monitoring, which is specific to Pelican crossings (i.e.
MCE0125, MCE0145 and Puffin) and is implemented in hardware on the T400 2-
phase drive card.
25.3.2 Overview
For earlier installations, a separate mains powered RLM unit may be employed. In this
case, the RLM facilities available are reduced. The combinations of facilities and
equipment which are available are summarised in the table below.
Equipment RLM Operation RLM Signals Available
free-standing RLM unit original RLM all red. RLF1, RLF2 & RLF3.
free-standing RLM unit enhanced RLM phase
delays and inhibits on
first RLM group only.
RLF1 & RLF2.
Caution:
RLF3 is not supported.
integral RLM unit original RLM all red. RLF1 & RLF2 for first
RLM group only.
RLF3 is not required.
integral RLM unit enhanced RLM phase
delays and inhibits.
RLF1 & RLF2 for up to
8 RLM groups.
RLF3 is not required.