T400 Controller Facilities Manual
667/EB/20200/000 Page A-6 Issue 9
Appendix APPENDIX A) .4) Using 27.5v Detector Supply - Cable Limitations
Table APPENDIX A) -9 to Table APPENDIX A) -12 indicate the permissible cable
lengths and whether 2 parallel cores are required for various detectors.
S = Single conductor out and return
P = Parallel conductors out and return
Assumes 1mm
2
cable.
NB: The following tables for distances assume the use of 1mm
2
cable with the detector
current specified. Use of larger cable will increase the length of run possible as
will use of detectors with a lower operating current. Recalculate any values as
required on a pro-rata basis.
The distances quoted are the ‘Maximum distance from the controller’.
Table APPENDIX A) -9) Number of Detector Boards (Siemens & Microsense) in
External Housing(s) Using a Common Cable (220mA per card)
Beehives:123456
Detectors:123456789101112
100m SSSSSSSSPPP
125m SSSSSSSPPPP
150m SSSSSSPPPPP
175m SSSSSPPPPP
200m SSSSPPPPP
225m SSSSPPPP
250m SSSPPPP
Table APPENDIX A) -10) Number of Detector Boards (Sarasota) in External
Housing(s) Using a Common Cable (370mA per card)
Beehives:123456
Detectors:123456789101112
100m SSSSPPPP
125m SSSPPP
150m SSPPP
175m SSPP
200m SSPP
225m S P P
250m S P P