T400 Controller Facilities Manual
667/EB/20200/000 Page 25-15 Issue 9
25.2.8 Fault Finding at the Outstation
Symptom Possible Reason
System Fault LED lit on T400
Main Processor
- Use handset to access fault log for information on the
type of fault that has occurred, this may be an Integral
Ancillary Processor fault.
Watchdog LED On - Software not running correctly. Attempt to discover
the cause using the controller handset commands OTS
and OTH, and then power off and back on.
OTU not replying to control
message
- OTU Switch settings incorrect.
- OTU configured incorrectly via the handset, repeat
configuration.
- Extended system bus cable disconnected or faulty.
- No control data - low line level, interference, or BT
lead disconnected/faulty.
The lamp monitor will not
learn the junction or will not
detect lamp failures
- There are entries in the fault log which indicate the
reason - e.g. faulty voltage monitor or its connections.
- The lamp monitor is not enabled (KLE handset
command).
- The controller’s signals are off.
- The lamp monitor connector is not connected to PLB.
- Use the KAC handset command to check the lamp
monitor is taking readings.
25.2.9 Lithium battery
The outstation PCB is fitted with a Lithium Battery (B1, part number
418/4/97186/000),
This battery must be Replaced every 4 years. The battery has a label attached to it
with the date by which the battery should be replaced. When replacing the battery,
label the new one with today’s date plus 4 years’.
WARNING: Care should be taken when handling/disposing of Lithium batteries.
Refer to code of practice CP526.
25.2.10 Recommended Spares
General Spares:
Ancillary Processor PCB 667/1/21611/001
(Note swap IC32 PLD and IC26 Firmware
EPROM, from old board to new board
when making replacement)
Lithium battery 418/4/97186/00
LMU Spares (if equipped):-
Current Transformer 667/7/25171/000
Voltage Monitoring Transformer 667/7/25172/000