T400 Controller Facilities Manual
667/EB/20200/000 Page 25-11 Issue 9
Current Transformers
Each controller phase or illuminated indicator that is to be monitored requires 1
current sensor as detailed below. The table also indicates which lamp feeds are passed
through the current sense transformer for each type.
Monitorable
Lamp/phase types
Current sensor
lamp feeds
Maximum number of
Signal Heads (see note 1)
Intersection Vehicle (IV) R, A, G 16 { 6 }
Pelican Vehicle (PV) R, A, G 16 { 6 }
Intersection Pedestrian (IP) Rm, Gm 16 { 6 }
Pelican Pedestrian (PP) Rm, Gm 16 { 6 }
Wait Indicator 40Watt (W4) Wt 16 { 6 }
Wait Indicator 60Watt (W6) Wt 16 { 6 }
Regulatory Sign (RS) Sign 7 signs (21 tubes)
{2 signs ( 6 tubes)}
Switched Sign
- Bulb type (SB)
Sign 16 lamps {6 (note5)}
Switched Sign
- Tube type (ST)
Sign 7 signs (21 tubes)
{2 signs (6 tubes) note 4 }
Pelican Pedestrian and
Wait (PPW and PP4)
Rm, Gm, Wt 16 (note 2)
{ 6 }
Pelican Stream
(PS and PS4)
R, A, G,
Rm, Gm, Wt
16 (note 3)
{ 6 }
Intersection Ped. & Wait
(IPW and IP4)
Rm, Gm, Wt 16 (note 2)
{ 6 }
Intersection Ped. Stream
(IPS and IS4)
R, A, G,
Rm, Gm, Wt
16 (note 3)
{ 6 }
Export Pedestrian
with flashing Red (XP1)
Rm, Gm 16
{ 6 }
Export Vehicle
with flashing Green (XV1)
R, A, G 16
{ 6 }
Export Vehicle Filter
flashing Amber Ball (XV2)
Flashing Ball 16
{ 6 }
Export Vehicle - flashing Amber
signal group (XV3)
R, A, G 16
{ 6 }
Note 1:
These limits apply to 240W rms supply voltage and 50W lamp loads (unless
stated). Where the supply is lower or the lamp loads are higher the limits are
reduced accordingly. For example the figures given in curly brackets {}, are the
maximum loads when a 50-0-50 Vrms mains supply is used. The limits are only
reduced if the actual voltage being monitored is at the lower level, i.e. if a 50-0-
50 Vrms supply (derived from a transformer) is used but the monitoring is on
the 240V rms side of the transformer, then the limits do not need to be
reduced.