Area Exit-Output S
P66E 1-2E 1-8E
(1 = Area A; 2 = Area B)
Sometimes it can be useful to extend the exit beeps, which occur at a keypad, to
be present on an audible device on the exit path. This option allows the exit beeps
during the arming of stay mode to be assigned to any of the 8 outputs. The Pulse
time (P39E) sets the length of each beep.
Option 1 = Output 1; Option 2 = Output 2 etc.
17.8 Area delinquency delay – arming activation indication
Area Delinquency Days
P67E 1-2E 0-99E
(1 = Area A; 2 = Area B) (Value 0-99 Days)
Each Area can have their own delinquency time. The delinquency time monitors
the arm/disarms of each Area. If an Area has not been armed within the set
number of days a delinquency report will be sent. Each time an Area is armed the
delinquency timer is reset. A value of 0 disables the delinquency monitoring.
If the default value of 0 is changed at this location (e.g. a value of 10 is entered meaning 10 days), the
next time the area is armed a delinquency restore message will be sent via the dialer (Event type 454)
as a test that the function is operating.
17.9 Automatic arm/disarm time zone
Area Arm Time Zone
P68E 1-2E 1-8E
(1 = Area A; 2 = Area B) (Value 1-8)
If option 2 or 3 are turned on location P46E then the Area can be automatically
armed or disarmed by a time zone/s. You can assign more than one time zone to
each Area. If assigning multiple time zones you should insure that they do not
overlap as this could cause confusion. A time zone would typically be 0830-1700
Monday-Friday. An area will turn on when the time zone ends (e.g. 1700) and turn
off when a time zone starts (e.g. 0830).
Option 1 = Time-Zone # 1 ; Option 2 = Time-Zone # 2 etc.