Dialer
125
Building Technologies
Fire Safety & Security Products
22.2 Auto answer ring count
Auto Ring Count
P175E 3E 0-99E
(Value 0-99)
If the dialer is set to answer an in-coming call for remote control or
upload/download the number of rings before answering the call can be set at this
location.
22.3 Test call options
Test Resync HHMM
P175E 4E 0000-2359E
(Value 0000-2359)
If the dialer is set to send Automatic Test Calls, the start time for the first call is set
at this location. This allows the test call to be linked to a quite period where the line
would not normally be used (e.g. 2300)
Test Period
P175E 5E 0-255E
(Value 0-255 Hours)
When reporting in Contact ID format the panel can send regular test calls to the
monitoring company to check the integrity of the panel and the line. The regularity
of the test calls is set at this location. It would normally be set to a value of 24 so
that a test call is sent one a day. The start time for the first test should also be set
at location P175E 5E. Check also the option P175E 2E 5E test call time period
change from hours to days.