Zones
114
Building Technologies
Fire Safety & Security Products
20.5 Vibration sensor zone type - zone response time
If a zone is used for connecting a hardwired vibration sensor, it could be necessary
to adjust the reaction time of the panel to the output signal of the vibration sensor.
Zone Response
P126E 1-8E 1-16E
There are 8 hardwired zone inputs on the panel. The response time (how quickly
the input responds to an input trigger) can be varied for each zone. The first 8
settings are very fast response times normally used when vibration sensors are
connected to a zone input. Response settings 1-8 (vibration) can only be applied to
zones 1-8 and the zone EOL setting must be set to Tamper 2k2 (Only the zone
options 125E 1-8E -3 or 12 or 14E. See chapter
20.4: Different End of Line (EOL)
Resistor value options).
If zone doubling is turned on, both zones on an input will have the same response time (e.g. zones 1
& 9 would have the same time).
The response settings 9-26 start at about 200ms for setting 9 (standard default
setting) through to 1.0 sec for setting 26.
If no exact timing is needed options 1-8 could be used as well.
Response
Setting
Reaction Time
Response
Setting
Reaction Time
1 Highest Vibration setting 17 600 ms
2-7 Middle Vibration setting 18 650 ms
8 Lowest Vibration setting 19 700 ms
9 200 ms 20 750 ms
10 250 ms 21 800 ms
11 300 ms 22 850 ms
12 350 ms 23 900 ms
13 400 ms 24 950 ms
14 450 ms 25 1000 ms
15 500 ms 26 1050 ms
16 550 ms