Miscellaneous installer and panel options
80
Building Technologies
Fire Safety & Security Products
14.3 Miscellaneous user options
Miscellaneous User Options
P25E 13E 1-8E
Option Display text Description
1 View Requires
Codes
Code required to view Memory: if this option is turned on, access to the event
memory will only be allowed by using an authorized code. The user must have the
permission (user rights) to view the memory and press
, enter Code and press
to have access to the event memory.
2 No Handover in
Stay
Cancel Handover Zone function in stay mode: if this option is turned on, any zone
defined as a handover zone will act as a normal delayed zone during stay mode (the
handover feature will be ignored). The zone will still have the normal handover
feature only in full arm condition.
3 Keypad Outputs
Disable if Armed
Output control from keypad is disabled when armed: this option denies the operation
to an output access control by an user while the area is armed.
4 Keypad Code
Disable if Entry
Keypad Codes are disabled during entry delay: using this option no codes will
operate during the entry delay. This forces the user to disarm before entering the
premises.
5 No Keypad
Indication if
Armed
No Keypad indications while armed: if this option is turned on and all areas assigned
to keypads, are armed, the keypad display will be blank during the arming condition.
If any keypad is assigned to both areas, both areas must be armed before the display
will go blank on arming.
- Up to version 9.07: Spare 6
Supervised
Output data to
bus
Valid as of version 9.07:
Monitored Keypad Bus Output Board: this option performs a similar function to option
6 at location P25E10E in that if it is turned on the Output status messages are sent to
the keypad bus. The difference with this option is when turned on the panel is
expecting the OutputX4 board connected to the keypad bus to acknowledge the
messages. If the OutputX4 does not acknowledge the output status messages the
panel will show an output board failure. This option should only be turned on if an
OutputX4 board (Version 1.1) is connected to the keypad bus.
According EN 50131-3 all units connected to the Control Panel should be monitored.
7 - Spare
- Up to version 9.07: Spare 8
Limit Report to 3
Events
Valid as of version 9.07:
Limit Events & Dialer to 3 of any one Type: if this option is turned on the panel will not
record any more than 3 events in memory for any event type during a single arm or
disarm cycle, e.g. if the AC.
Failed 4 times while armed or disarmed the panel will only record the AC fail 3 times
in memory.
And will only report the AC fail 3 times to the dialer. As soon as the arm state has
changed any count are reset back to zero again. If this option is off there is no limit on
the recording and reporting of Events.
According EN 50131-3 the events of the same type should be limited to 3.