Zones
109
Building Technologies
Fire Safety & Security Products
20 Zones
20.1 Zone area assignment
Zone Areas
P121E 1-16E 1-2E
Option Display text Description
1
Area A
Area A: this option assigns the Zone to Area A. If a Zone is assigned only to Area A it
will activate if Area A is armed. If the zone is in both area A & B then it will activate
only when both areas are armed.
2
Area B
Area B: this option assigns the Zone to Area B. If a Zone is assigned only to Area B it
will activate if Area B is armed. If the zone is in both area A & B then it will activate
only when both areas are armed.
There are more options to choose but the System supports only 2 Areas (1-2)
20.2 Zone type options- basic information
Zone A Options
P122E 1-16E 1-8E
Option Display text Description
1
Active
Zone is Active: if this option is on the zone is turned on. If it is turned off the zone will
not be monitored by the panel. The panel can provide up to 16 zones but is
configured by default as an 8 zone panel with this option turned off for zones 9-16.
2
Normally open
Zone is N/O: this option only applies if the zone input is set to type 14 (zone doubling)
at location P125E. When configured as type 14 there are three resistors wired in
series on the input, a 2k2 tamper resistor, a 4k7 low zone resistor and an 8k2 high
zone resistor. At this point, the zone can be set as having a N/C (Normally closed)
alarm contact where the EOL resistor is shorted out in the sealed state or it can be set
as a N/O (Normally open) alarm contact where the EOL resistor is in circuit in the
sealed state. If this option is turned on it assumes that the alarm contact is N/O.