Contact ID code summary
141
Building Technologies
Fire Safety & Security Products
26 Contact ID code summary
Normally the Contact ID signal identification codes which are used by a monitoring
station are used from the standard list. The system is programmed by default with
the equivalent standard formats (3 digit numbers). Nevertheless if the control panel
should report different formats it is described here how to change it.
26.1 Change Zone Contact Identification (CID) report codes
Zone Alarm CID code
P157E 1-16E XXXE
(3 digit event code)
Normally a zone alarm would default to reporting a standard Burglar Alarm code of
130 when the zone activates. If the zone is not being used as a burglar alarm and
you need to identify the correct type of alarm event you can change the event code
at this location (e.g. if zone 5 was a fire sensor you could program a value of 110 at
P157E 5E).
Zone Near Alarm CID
P158E 1-16E XXXE
(3 digit event code)
If the Near & Confirmed zone alarm reporting option was active the default report
code for a Near Alarm is 138 when the zone activates for the first time. There
should be no reason to change this code but if some special application was to be
used it can be changed at this location.
Zone Confirmed Alarm CID
P159E 1-16E XXXE
(3 digit event code)
If the Near & Confirmed zone alarm reporting option was active the default report
code for a Confirmed Alarm is 139 when a second zone activates within 60
minutes of the near alarm. There should be no reason to change this code but if
some special application was to be used it can be changed at this location.