Zones
111
Building Technologies
Fire Safety & Security Products
Zone B Options
P123E 1-16E 1-8E
Option Display text Description
1
Handover
One is a Handover Zone: a Handover Zone is one that its entry delay will apply
provided a Non-Handover entry zone is triggered first. If no other entry delay zones
are triggered before the handover zone the entry delay on that zone does not apply
and the alarm will become instant (no entry delay).
2
Dual Trigger
Zone is a Two Trigger Zone: if this option is on the zone will have to trigger twice
within the two trigger time (P25E 5E) before it will cause an alarm. If the zone does
not trigger a second time before the two trigger time expires, the count is reset and it
will take another two triggers to cause an alarm on this zone. If more than one zone is
set-up as a two trigger zone, then a single trigger from two separate zones within the
two trigger time can also cause an alarm. If the zone becomes faulty and stays in
alarm once triggered it will also cause an alarm provided it remains in alarm for
longer than the two trigger time.
3
24 Hour
Zone is a 24 Hour Zone: if this option is on the zone will be constantly monitored
regardless of the arm/disarm state of the panel. If the 24 Hour zone also has an entry
delay programmed (P144E), this delay will apply. If the 24 Hour zone activates but
then resets before the entry delay expires no alarm will be generated. This feature
can be useful for monitoring plant type alarms such as freezer alarms. Once the
alarm has been generated it must be cleared by entry of a valid User code.
4
24 Hour Auto
Reset
Zone is a 24 Hour Auto-reset Zone: if this option is on the zone will be constantly
monitored regardless of the arm/disarm state of the panel. If the 24 Hour zone also
has an entry delay programmed (P144E), this delay will apply. If the 24 Hour zone
activates but then resets before the entry delay expires no alarm will be generated.
Once an alarm has been generated with a 24 Hour Auto-reset zone, the alarm will be
removed automatically once the input reseals.
5
24 Hour Fire
Zone is a 24 Hour Fire Zone: if this option is on the zone will be constantly monitored
regardless of the arm/disarm state of the panel. If the 24 Hour Fire zone also has an
entry delay programmed (P144E), this delay will apply. If the 24 Hour Fire zone
activates but then resets before the entry delay expires no alarm will be generated.
Once the alarm has been generated it must be cleared by entry of a valid User code.
The 24 Hour Fire Zone will also cause an alarm output to pulse the alarm to
differentiate a fire alarm from a burglar alarm (e.g. a fire alarm will switch the output
on and off at the pulse timer rate whereas a burglar alarm on the same output will
sound continuously).
6
-
Spare
7
Activate Chime
Zone is a Chime Zone: if this option is on, the zone will operate Chime mode when
disarmed. When the alarm is armed the Chime Mode is disabled for this zone. A
Chime zone can sound the keypad buzzer or operate an output to indicate that the
zone is unsealed. It is normally used to monitor areas during the daytime.
8
Always Chime
Zone is a Permanent Chime Zone: if this option is on, the zone will operate Chime
mode when armed or disarmed. When the alarm is armed the zone will continue to
only be a Chime Mode Zone and will not cause a burglar alarm. A Chime zone can
sound the keypad buzzer or operate an output to indicate that the zone is unsealed.