Zones
113
Building Technologies
Fire Safety & Security Products
20.4 Different End of Line (EOL) Resistor value options
There are 8 hardwired zone inputs on the panel. Each of these inputs can have
different EOL (End-of-Line) configurations if desired. As standard is supplied:
z 2K2 for Tamper
z 4k7 for Detectors Zone 1-8 (low zone)
z 8k2 for Detectors Zone 9-16 (high zone)
Therefore programming Zones as type 14 is recommended – P125E 1-8E 14E
If requested by the installation (e.g. already existing mounted detectors with other
EOL resistor values), the control panel Sintony 60 supports in addition different
single resistor values (wiring Types 1-11), can provide 8 zones with tamper (wiring
Types 12, 13), zone doubling to allow for up to 16 zones plus tamper (wiring Type
14), or zone doubling without tamper (wiring Type 15). (Refer to chapter
4.3.2:
Zone wiring examples).
Zone EOL Mode
P125E 1-8E 1-15E
Zone EOL
Type P125E
Input Resistor Comments Wiring options
1 1k (Brown, Black, Red) Single EOL Type 1-11
2 1k5 (Brown, Green, Red) Single EOL Type 1-11
3 2k2 (Red, Red, Red) Single EOL Type 1-11
4 3k3 (Orange, Orange, Red) Single EOL Type 1-11
5 3k9 (Orange, White, Red) Single EOL Type 1-11
6 4k7 (Yellow, Violet, Red) Single EOL Type 1-11
7 5k6 (Green, Blue, Red) Single EOL Type 1-11
8 6k8 (Blue, Grey, Red) Single EOL Type 1-11
9 10k (Brown, Black, Orange) Single EOL Type 1-11
10 12k (Brown, Red, Orange) Single EOL Type 1-11
11 22k (Red, Red, Orange) Single EOL Type 1-11
12 2k2 Tamper, 4k7 Zone Zone & Tamper Type 12-13
13 3k3 Tamper, 6k8 Zone Zone & Tamper Type 12-13
14
2k2 Tamper,
4k7 Low Zone,
8k2 High Zone
Zone Doubling,
with Tamper
Type 14
15
4k7 Low Zone,
8k2 High Zone
Zone Doubling,
no tamper
Type 15
To program the zone there are only 1-8 options, because there are only 6 hard wired inputs on the
control panel. To program the zones 9-16 this have to be done through Zone doubling (Options 14 or
15) again on the zone inputs 1-8. (e.g. if the panel should be used with 16 single identifying zones, all
EOL options (1-8) must be programmed as Zone doubling type 14 or 15)