Keypads
103
Building Technologies
Fire Safety & Security Products
18.8 Keypad to output mask
Keypad User Output Mask
P82E 1-8E 1-8E
A Keypad can be assigned to an output or multiple outputs. If a Keypad is not
assigned to an output a User cannot turn that output on or off from the Keypad.
This feature is useful when using the access control features of the panel.
E.g. a User may be allowed to operate more than one output with their code but
they will be limited to just the output assigned to the Keypad they are using.
Option 1 = Output 1; Option 2 = Output 2 etc.
18.9 Control button to output mask
Keypad Control Mask
P83E 1-8E 1-8E
The
C
tr
l
button at a Keypad can be assigned to an output or multiple outputs. If the
C
tr
l
button is not assigned to an output a User cannot access Local Control Mode
(by pressing the
C
tr
l
button) and turn that output on or off from the Keypad. This
feature is useful if outputs are being used to control devices such as lights, etc and
you wish to be able to turn them on or off from a keypad. By limiting the access to
outputs via the
C
tr
l
button you can avoid conflict with alarm outputs.
E.g. the User can be denied access to outputs that are being used for alarm
functions.
Option 1 = Output 1; Option 2 = Output 2 etc.
18.10 Keyboard panic, fire and medical alarms to outputs and KP
buzzer
The following options for Panic, Fire and Medical Alarms can also be programmed to a Card reader
with Keypad buttons- (0-9). Therefore there are always two options mentioned in the description.
(e.g.
& or
Ctrl
& )
Keypad Panic Outs
P84E 1-8E 1-8E
(includes
& or
C
tr
l
& )
A Keypad generated Panic Alarm (either pressing button,
& or
C
tr
l
&
together) can be assigned to an output or multiple outputs. This can be used to
operate an audible or visual alarm connected to the output.
Option 1 = Output 1; Option 2 = Output 2 etc.