Outputs
87
Building Technologies
Fire Safety & Security Products
Output Flash Time
P39E 1-8E 0-255E
(0-255 1/10
th
Seconds, e.g. 20 = 2 sec.)
The Pulse time affects the time the output turns on when the pulse timer is used on
the output. The pulse time is in 1/10
th
second increments so that very quick timing
can be achieved. Functions like radio key arm/disarm chirps to an output or a
flashing output (P34E option 2), all use the pulse timer. If access tags are assigned
with the chirp function (P46E 4E) and the LED on an access reader is set to follow
an output with the chirps assigned (P98E) then this timer must be set to a minimum
value of 10 for the reader LED to display the chirps.
Output Reset Time
P40E 1-8E 0-9999E
(0-9999 Seconds, 0 = latched output)
The Reset time affects the time the output turns on when an alarm is active. The
default range is 0-9999 seconds but if option 2 at location P37E is on the range is
0-9999 minutes.
Output Chime Time
P41E 1-8E 0-255E
(0-255 1/10
th
Seconds, e.g. 20 = 2 sec.)
The Chime Mode time affects the time the output turns on when a Chime Zone is
activated. The Chime time is in 1/10
th
second increments so that very quick timing
can be achieved.
16.3 Output voice board remote control start message
Output Messages
P42E 1-8E 0-99E
(0-99)
If a Voice Board is connected to the panel it is possible to dial the panel from a
remote telephone and turn outputs on or off using a 4 digit code with voice prompts
provided by the Voice Board to identify what function you are controlling. Refer to
the separate Voice Board programming manual for more details.
16.4 Un-map an output
Un-map Output
P43E 1-8E
If you are using an output for a special purpose and do not need the standard
defaults assigned to that output you can remove all defaults at this location. For
example if you are using output number 4 to open a door via a Remote control and
you don’t want any alarms to be assigned to the output press P43E 4E and ALL
defaults will be removed. This removes all options assigned to the output and
makes the reset time 0 for latched operation