Outputs
84
Building Technologies
Fire Safety & Security Products
16 Outputs
16.1 Output options
With all output programming options we refer to outputs 1-8. Only outputs 1-4 are available as
standard, with outputs 5-8 requiring the connection of the optional Output module 12V/1A IRO6-04
unit that connects to the keypad bus ( the output module provides 4 change-over relay contacts).
Output A Options
P34E 1-8E 1-8E
Option Display text Description
1
Inverted
Invert Output: this option is used to invert the normal state of the output. The panel
uses open collector transistor switches and the default state of all outputs is off
(open). When in alarm the transistor is turned on and the output goes low (0V). The
invert option reverses this function.
2
Flash
Flash Output: when the output is turned on this option causes the output to flash at a
rate set by the pulse timer (P39E). One use is to flash a lamp during an alarm. DO
NOT turn this option on if the Output is to be manually controlled by a user or the
C
tr
l
button.
3
Single Pulse
Single Pulse to Output: this option produces a single pulse at the output when an
alarm occurs (the pulse time is the value programmed at the output pulse timer
P39E).
4
Retrigger able
Lockout Output: this option is used to limit the output to one operation per arming
period.
5
DTMF controlled
DTMF Remote Control of Output: if the panel is set-up so a User can dial in from a
remote telephone to perform DTMF Code Control (P175E 12E) of the Outputs, this
option selects which Outputs are able to be controlled by the remote user.
6
User code to
Output
Keypad User can Operate Output: if a DTMF Output control code is programmed into
the panel (P175E 12E), the same code can be entered at the panel keypad to allow
local control of the Outputs selected at this address.
7
<Control> to
Output
<Control> button can Operate Output: the
C
tr
l
button on the keypad can also be used
to turn outputs on or off. For that to happen this option must be turned on for the
output/s concerned. To turn an output on locally at the keypad the operator simply
presses the
C
tr
l
button for 2 seconds and the word Outputs will appear on the LCD
keypad to indicate that the Control mode is active. If any controllable outputs are
currently on they will be indicated at the keypad. The operator can now press a button
relating to the output/s they wish to control e.g. pressing the
button will turn output
1 on or off. The
button for output 2 etc. When finished the operator then presses
the
button to cancel the Control mode and return to normal
8
Chime Flash
Pulsed Chime Mode Alarm: Chime Zones programmed to this output will turn the
output on for the duration of the Chime to Output time period (P41E). If this option is
on the output will pulse at the pulse timer rate (P39E) for the duration of the chime
zone to output timer (P41E).