Dialer
123
Building Technologies
Fire Safety & Security Products
22 Dialer
22.1 Dialer options
Dialer A Option
P175E 1E 1-8E
Option Display text Description
1
Enable Dialer
Dialer is Enabled: if this option is turned on the dialer will be enabled. The option
must be on to allow the dialer to make calls.
2
Fax Defeat
Fax Defeat: the panel can automatically answer an in-coming call in two ways. The
first is to set the auto-answer ring count to a convenient number (P175E 4E) and let
the phone ring until this number is reached at which time the panel will answer the
call. The second method is to use fax defeat which entails calling the panel and
letting it ring no more than 4 times, hanging up, then ringing back within 45 seconds.
The panel will now answer the call on the first ring.
3
Ignore Line Fail
Disable Telephone line Monitoring: if the panel is connected to a poor telephone line
and the line failure alarm is appearing regularly, by turning this option on the panel
will not do the line test.
4
Decadic Dialer
Pulse Dial: if this option is Off the panel will dial in DTMF format, if On then the panel
will dial using Pulse Dialing format
5
Reverse Decadic
Reverse Pulse Dial. if this option is On, and option 4 is On, then the panel will dial
using Reverse Pulse Dialing format (e.g. the number 9 = 1 pulse). If this option is Off
and Option 4 is On, the panel will dial in normal Pulse format (e.g. the number 9 = 9
pulses).
6
Long Dial Tones
Long DTMF Dialing Digits: if this option is Off, the panel will dial using normal dialing
(75ms on & 75ms off). If it is On, the panel will dial using the long tones (100ms on &
100ms off).
7
Modem
AutoDetect
Auto-detect Modem: if this option is on the panel will answer an in-coming call with
the V21 acknowledge tone. If the modem does not respond within 5 seconds the
panel will then generate the acknowledge tones for BELL103 format. It will repeat this
cycle twice and then hang-up if no communication with a modem is established
8
Modem
Force V21
Force V21 Mode: the dial up panel to PC link can be established using either Bell 103
or V21. If the auto-detect function at option 7 does not result in the best format for
your modem then you can force the panel to only communicate in one format. If the
LED is off the format is BELL103, LED on means V21.