Time and date setting
82
Building Technologies
Fire Safety & Security Products
15 Time and date setting
The alarm system has an internal clock that may be used to automatically arm or
disarm the alarm or turn outputs on or off. It is also used to identify when events
have occurred in the memory via the LCD keypad. Therefore the Sintony 60 is
equipped with a RTC-Real time clock which is powered up separately by a battery
on the PCB. Ensure this is set correctly at the time of installation so that the all of
the functions using the time have will work correctly.
15.1 How to set time and date
Time HH:MM
P26E 1E
(Value 0-2359)
Week Day 1-7
P26E 2E
(Value 1-7) [where 1 = Sunday, 2 = Monday, 3 = Tuesday, etc]
Date DDMMYY
P26E 3E
(Value DDMMYY) (for example 020906 = 2
nd
September, 2006)
The Real Time Clock controls the Time-zones, the timing of automatic test calls
and is used to Time & Date stamp the events in the Event Buffer. The clock is
programmed in 24 hour format (e.g. 00:00-23:59).
15.2 Daylight saving (winter/summer time), DLS settings
If Daylight Saving (DLS), change from winter to summer time, is used, the actual
start and stop details can be entered here and the clock will automatically adjust for
Daylight Saving.
Daylight Saving Status
P26E 4E 1E
This function activates the automatic change in the time.
If you are in Daylight Saving Time when the alarm system is installed you MUST turn on option 1 at
location P26E 4E so that the panel knows that Daylight Saving Time is currently active. Failure to do
this will not allow the clock to automatically adjust to the correct time when Daylight Saving Time
(winter-Summer time) ends