System overview
26
Building Technologies
Fire Safety & Security Products
2k2 (Red, Red, Red) for tamper
To overtake existing installation with already build in different resistor values, the Sintony 60 could
also be programmed to different values (see chapter
20.4: Different End of Line (EOL) Resistor value
options; P125E).
If an iInput is programmed as a wireless input, the system will ignore all hardwired connection to this
input and look only for the radio signal! (see chapter
20.2: Zone type options- basic information; Zone
A Options, option 5; P122E)
4.3.2 Zone wiring examples
The connection of each device depends on the type of switch which is used in the
detectors. We differentiate between:
z N/C normally closed, requires serial connection
z N/O normally open, requires parallel connection
Option 1: Only one EOL- end of line resistor
Fig. 9 Type 1-11 - Single EOL no Tamper
The zone input must be programmed as single resistor value (see chapter
20.4:
Different End of Line (EOL) Resistor value options; options 1-11; P125E). The
tamper contact should be monitored separately with the same connection schema
(tamper input).
Option 2: Installation with 1-8 Zones with Tamper monitoring
Fig. 10 Type 12 Single Zone with Tamper
The Zone input must be programmed as zone with tamper (see chapter
20.4:
Different End of Line (EOL) Resistor value options; option 12; P125E).