Telephone numbers
136
Building Technologies
Fire Safety & Security Products
Option Display text Description
8
Divert if Button
Divert on single button <Arm> or <Stay>: if this option is on then the Call-Divert On
number (P194E 1E) will be dialed when the system is Armed with the
or
buttons. This option must be selected if the Call Divert function is required and single
button arming is being used.
Divert Options
P193E 1-2E 1-8E
(1 = Divert ON Number; 2 = Divert OFF number)
Option Display text Description
1 - Spare
2 - Spare
3
Blind Dial
Blind Dial: when the dialer makes a divert call it looks for dial tone before making the
call. If no dial tone is detected the panel hangs up and attempts another call. The
panel will do this 3 times and if dial tone is still not detected it will make the call
anyway. If blind dial is on, the panel skips the dial tone detection and dials 4 seconds
after looping the line (used where non standard or low level dial tone exists).
4 - Spare
5 - Spare
6 - Spare
7
Use Dial Prefix
Use the Dial Pre-fix Number: if the Divert number does not provide sufficient digits for
dialing purposes it is possible to program a dial pre-fix number (P175E 8E). The pre-
fix can be dialed before the divert number. Turning this option on dials the pre-fix first
followed by the divert number.
8 - Spare