Engineer programming via the keypad
14.5.3.4 EDIT EXPANDERS
To edit expanders:
1. Scroll to EXPANDERS > EDIT.
2. Press SELECT.
3. Scroll to the device to be edited and press SELECT.
Parameters and details, if applicable, are displayed for editing as shown in
the table below.
4. Press BACK to exit the menu.
STATUS (ONLINE/OFFLINE), SERIAL NUMBER, VERSION, POWER, INPUT
STATE, PSU, AUX FUSE, ADDRESS INFO (MANUAL/AUTOMATIC)
DESCRIPTION
INPUT>SELECT ZONE
KEYPAD (Indicator Expander Only)
FUNCTION KEYS (Indicator Expander Only)
LED ALWAYS (Indicator Expander Only)
MODE (LINKED/FLEXIBLE) (Indicator Expander Only)
VISUAL INDICATIONS (FLEXIBLE MODE) (Indicator Expander Only)
AUDIO INDICATIONS (FLEXIBLE MODE) (Indicator Expander Only)
DEACTIVATION (FLEXIBLE MODE) (Indicator Expander Only)
LOCATION (Keyswitch Expander Only)
LATCH (Keyswitch Expander Only)
VISUAL INDICATION (Keyswitch Expander Only)
DEACTIVATION (Keyswitch Expander Only)
FUNCTION KEYS (Keyswitch Expander Only)
AUX. CHANNEL (Audio Expander Only)
VOLUME LIMIT (Audio Expander Only)
For naming and identifying, expanders are allocated zones (in groupings of 8)
with subsequent identities of 1 to 512. (The greatest number in zone identification
is 512.) Therefore, any expander named or identified by a number greater than 63
has no allocated zones.
14.5.3.5 EDIT DOOR CONTROLLERS
For further information about Door controller see page [➙ 39].
1. Scroll to DOOR CONTROLLERS > EDIT.
2. Press SELECT.
3. Scroll to the device to be edited and press SELECT.
Parameters and details, if applicable, are displayed for editing as shown in the
table below.
Name of the door controller