Engineer programming via the keypad
14.11.2 WALK TEST
A walk test ensures that the sensors are operating correctly on the SPC system.
To perform a walk test:
1. Scroll to TEST > WALK TEST.
2. Press SELECT.
3. The display indicates the number of zones to be tested on the system with the
text TO TEST XX (where XX is the number of valid walk test zones). Locate the
sensor on the first zone and activate it (open the door or window).
The keypad buzzer sounds continuously for approximately 2 seconds to
indicate that the zone activation has been detected and the number of
zones left to test (displayed on the keypad) decreases.
4. Continue with the remaining zones on the system until all zones have been
tested. If a zone activation does not get acknowledged by the system, check
the wiring of the sensor and/or replace with another sensor if necessary.
All zones can be included in an Engineer walk test.
14.11.3 ZONE MONITOR
The Zone Monitor option displays status information on each of the zones on the
system.
To view zone status information:
1. Scroll to TEST > ZONE MONITOR.
3. Scroll to a preferred zone and press SELECT.
The status of the zone and its associated resistance value is displayed.
4. Press NEXT to locate the zone (e.g. CONTROLLER 1 = first zone on
Controller).
Refer to the table below for correlating status information (valid for Dual EOL
resistors).
All zones on a system can be monitored for correct operation by performing a
monitoring test.
To perform a zone monitoring test:
1. Scroll to ZONE MONITOR.