Engineer programming via the browser
6. Click Download again.
When downloading a configuration file, the configuration settings are stored in a .cfg
file. This file can then be uploaded to other controllers to avoid lengthy programming
procedures.
Upload or test an audio file to the SPC. The file must be created by the SPC Pro
Audio Manager.
Fast Programmer File Operations.
Upgrades the controller and peripheral firmware.
Note: Manufacturer Access is required for this operation. See System Options. [➙
156]
Restores the SPC system to factory defaults.
NOTICE! The IP address is maintained for connecting to the web interface after a
factory default from the web page
A custom language can be created by a customer or local distributor using a
translation tool provided by Siemens. This option enables the custom language file to
be uploaded. Refer to page ?? for details on how to activate the custom language on
the panel.
The panel must be licensed for use of custom languages and with other languages
other than English.
Note: This language applies to the panel firmware only and is not available for SPC
Pro or SPC Safe.
15.6.1 Upgrading Firmware
Manufacturer Access is required for these operations and when enabled, is
available for the completion of both controller and peripheral firmware upgrades.
See System Options [➙ 156].
Firmware for SPC is contained in two separate files:
Controller Firmware File
Contains the firmware for the controller’s CPUs only. Filename has the
extension *.fw.
Peripheral Firmware File
Contains the firmware for the X-BUS nodes, plus PSTN and GSM modems.
.Filename has the extension *.pfw.
The two files are upgraded separately.
Note: Firmware can also be upgraded using SPC Pro and the Fast Programmer.
To upgrade firmware on the system:
Select the Firmware option from the File page.
The following Firmware File Operations page is displayed: