Engineer programming via the browser
Timers
Designation of the functions in the following order:
1
st
row: Web/SPC Pro
2
nd
row: Keypad
Internal Bells
INT BELL TIME
Duration that internal sounders will sound when alarm is
activated. (1 – 15 minutes: 0 = never))
External Bells
EXT BELL TIME
Duration that external sounders will sound when alarm is
activated. (1 – 15 minutes; 0 = never)
Ext. Bell Delay
EXT BELL DELAY
This will cause a delayed activation of the external bell. (0 –
600 seconds)
Ext. Bell Strobe
STROBE TIME
Duration that the strobe output will be active when an alarm is
activated. (1 – 15 minutes; 0 = indefinitely)
Number of seconds that a chime output will activate, when a
zone with chime attribute opens. (1 – 10 seconds)
Double Knock
DKNOCK DELAY
The maximum delay between activation’s of zones with the
double attribute, which will cause an alarm. (1 – 99 seconds)
The number of days a zone remains under soak test before it
automatically returns to normal operation. (1 – 99 days)
Mains Delay
MAINS SIG DELAY
The time after a mains fault has been detected before an alert
is activated by the system. (0 – 60 minutes)
Dialer Delay
DIALER DELAY
When programmed, the dialler delay initiates a predefined
delay period (0 -30 seconds) before the system dials out to an
Alarm Receiving Centre (ARC). This is specifically designed
to reduce unwarranted responses from Alarm Receiving
Centres and the constabulary. In the event of a subsequent
zone being tripped the dialler delay period is ignored and the
dialler dials out immediately. (0 – 30 seconds)
Keypad Timeout
KEYPAD TIMEOUT
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10 – 300 seconds)
Keypad Language
KEYPAD LANGUAGE
The duration a keypad will wait in idle before switching
language to default ( 0 - 9999 seconds; 0 = never).
Engineer Access
ENGINEER ACCESS
The timer for the Engineer access starts as soon as the user
enables the Engineer Access. (0 – 999 minutes. ‘0’ indicates
no time limitation for system access)
Bell on Fullset
FULLSET BELL
Activates the external bell momentarily to indicate a full set
condition. (0 – 10 seconds)
Strobe on Fullset
FULLSET STROBE
Activates the strobe on the external bell momentarily to
indicate a full set condition. (0 – 10 seconds)
The Final Exit time is the number of seconds that arming is
delayed after a zone programmed with the final exit attribute
is closed. (1 – 45 seconds)
Number of seconds to delay triggering of tech. zones with