Engineer programming via the keypad
COMMUNICATION
102
Siemens AB
A6V10276959
Security Products
18.11.2011
14.10.2 ETHERNET PORTS
To program the Ethernet port:
1. Scroll to ETHERNET PORT.
2. Press SELECT.
The IP ADDRESS option displays, XXX.XXX.XXX.XXX For single digits,
leading zero(s) are required. Ie., 001
3. Press SELECT and enter the preferred IP address.
When the ENTER key is operated, the system beeps twice and states
UPDATED if the IP address is valid. If the IP address is allocated manually,
then this must be unique on the LAN or VLAN, connected to panel. A value
is not entered if the DCHP option is used.
4. Scroll to IP NETMASK.
5. Press SELECT and enter the IP NETMASK format XXX.XXX.XXX.XXX. (For
single digits, leading zero(s) are required. Ie., 001) When the ENTER key is
operated, the system beeps twice and states UPDATED if the IP NETMASK is
valid.
6. Scroll to GATEWAY. Note the gateway needs to be programmed for access
outside the network (for use with the Portal).
7. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For
single digits, leading zero(s) are required. Ie., 001) When the ENTER key is
operated, the system beeps twice and states UPDATED if the GATEWAY is
valid.
8. Scroll to DHCP. The DHCP is enabled if the LAN has a DHCP server to
allocate the IP address. The IP address is to be enabled manually. Note the
gateway needs to be programmed if the panel needs access outside the
network (for Portal service).
9. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For
single digits, leading zero(s) are required. Ie., 001)
When the ENTER key is operated, the system beeps twice and states
UPDATED if the GATEWAY is valid.
The DHCP option is displayed.
10. Toggle between DHCP ENABLED and DISABLED for preferred option.
11. Press SELECT.
14.10.3 MODEMS
The SPC system supports SPC intell-modems for communications with analogue
lines and mobile network interfacing for enhanced communications and
connectivity. The SPC system must be configured accordingly.
NOTICE
Before changing PIN or new SIM card, ensure all power sources are
disconnected (AC mains and battery) or card will not be activated.