
Engineer programming via the browser
Configuring controller inputs & outputs
This output is latched so it will remain active until restored by a level 2 user.
PIR Masking is logged by default. The number of log entries do not exceed 8 between
arming periods.
This output turns on if there are any inhibited, isolated, or walk test zones on the
system
This output turns on if there is a failure to communicate to the central station
This output turns on a ‘Man Down’ wireless device which is activated during a ‘Man
Down’ test.
This output is activated if the system is in Unset mode.
This output activates if an alarm abort event occurs i.e. when a valid user code is
entered via the keypad after a confirmed or unconfirmed alarm. It is used, for example,
with external dialers (SIA, CID, FF)
This output is used to activate a manual or automatic test on a seismic zone. Seismic
sensors have a small vibrator that will be attached to the same wall as the sensor and
is wired to an output on the panel or one of its expanders. During the test, the panel
waits up to 30 seconds for the seismic zone to open. If it does not open, the test fails. If
it opens within 30 seconds the panel then waits for the zone to close within 10 seconds.
If that doesn’t happen, the test fails. The panel then waits a further 2 seconds before
reporting the test result. The result of the test, either manual or automatic, is stored in
the system event log
This output activates on a local intrusion alarm.
This output activates when a Fob or WPA button is pressed.
This output activates when there is a line fault on the primary modem..
This output activates when the primary modem fails.
This output activates when there is a line fault on the secondary modem.
This output activates when the secondary modem fails.
This output activates when the battery is low,
This output activates if an ‘All Okay’ entry procedure is implemented and there is no
alarm generated i.e. the ‘All Okay’ button is pressed within the configured time after the
user code is entered.
This output activates if an ‘All Okay’ entry procedure is implemented and a silent alarm
generated i.e. the ‘All Okay’ button is not pressed within the configured time after the
user code is entered.
*
This output type can only indicate system wide events (no area specific events).
15.9.3 Configuring system latch and auto set outputs
Click on the Edit button for the Output Configuration option in System Options.
The following screen is displayed:
Comentarios a estos manuales