Engineer programming via the keypad
2. Press SELECT.
3. Scroll to a preferred zone and press SELECT, or enter the zone number
directly.
If the zone is located close to the keypad, the status of the keypad can be
viewed as it changes. The Zone status and resistance value displays on
the top right.
4. Change the state of the sensor; e.g. for a door contact sensor, open the door.
The keypad buzzer beeps and the status of the sensor changes from CL
(Closed) to OP (Open). The corresponding resistance value changes to a value
that depends on the EOL resistance scheme.
It is advisable to check the operation of all zones on the system after installation
is complete. To locate the zone select NEXT (bottom right) on the keypad. A zone
status value of SH or DI indicates that the zone is shorted or disconnected.
14.11.4 OUTPUT TEST
To perform an output test:
1. Scroll to OUTPUT TEST.
2. Press SELECT.
3. Toggle between CONTROLLER and EXPANDER for preferred option.
4. If testing the controller outputs, scroll to the preferred output and press
SELECT. If testing the expander outputs, select the expander and then the
output.
The keypad display indicates the current state of the output on the top line.
5. Toggle the output state ON/OFF.
6. Check that the device connected to the selected output changes state
accordingly.
14.11.5 SOAK TEST
A Soak Test provides a method of putting selected zones on test. Zones on soak
test do not cause any alarms but are recorded in the event log. Zones on soak test
will remain on soak test until the soak test timer expires as in the timers default (14
days).
To perform a soak test:
1. Scroll to SOAK TEST and press SELECT.
2. Toggle between ENABLE SOAK and CANCEL SOAK for preferred option.
3. Scroll to preferred zone and press SELECT.
A message confirming that the zone is in soak is displayed.
All zone types can be included in a Soak test.