Engineer programming via the browser
Configuring zones, doors and areas
176
Siemens AB
A6V10276959
Security Products
18.11.2011
15.8.2.9 Area Triggers
The Triggers section is only displayed if triggers have been defined previously.
(See section on Triggers)
Click on the Edit button to add, edit or delete trigger conditions for the area. The
following page is displayed:
Configure the trigger for the area using the following parameters:
Trigger
Select a trigger from the drop down list.
Edge
The trigger can activate from either the positive or negative
edge of the activation signal.
Action
This is the action that is performed when the trigger is
activated. Options are:
Unset
Partset A
Partset B
Fullset
Delay autoset
This action will delay alarm setting when the autoset
timer is running. The trigger will only add time if the Delay
Limit has not been exceeded and each trigger activation
will delay setting by the time defined in Delay Interval
(see section Setting/Unsetting [170].
Restore alarms
This action will clear all alarms in the configured zone.
Note: Triggers cannot be configured from a keypad.
See also
Triggers [ 239]