Applicable attributes to zone types
NOTE: The Technical Output will not trip until the delay timer has expired.
Openings are reported only in armed mode.
If enabled and a fire alarm occurs, a Fire Pre-alarm timer is started and
internal bells and buzzers are activated. (See Timers [➙ 160].) If the alarm is
not cancelled within the timer duration, a fire alarm is confirmed, internal and
external bells are triggered and an event is sent to ARC.
If enabled, a Fire Recognition timer is activated which adds extra time to the
Fire Pre-alarm timer duration until a file alarm is reported for the zone. See
Timers [➙ 160].
Seismic Test/Automatic Sensor
Test
A Seismic zone type may be tested manually or automatically. This attribute
allows automatic testing to be enabled. Refer to the section on timers [➙ 160]
for details of how to configure the timer that determines how often the panel
tests any seismic zones that have this attribute set. The default value for the
timer is 7 days.
The ‘Delayed Setting’ attribute is used for Key Arm zones to delay the setting
of an area. The delay follows the exit timer for the area to which the key arm
is associated.
Select the configured verification zone to assign to this zone to trigger
audio/video verification.
21.18 Applicable attributes to zone types
The following table shows which attributes are applicable to each zone type: