Overview of alarms 06/2007
PLC alarms
2-338
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007 Edition
2.4 PLC alarms
400000 PLC STOP [Type]
Definitions: PLC not in cyclic mode. Travel with the machine is not possible.
[Type]: 1 Ready(User program has not been started)
2 Break (User program has been interrupted)
3 Error (Other PLC alarm with PLC Stop active)
Reaction: Alarm display.
Remedy: Rectify other PLC alarm;
Switch on menu in PLC stop position
or test user program.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
400002 System error [Type]
Definitions: [Type]: Type number
Internal error states are displayed with this alarm. An error number is also specified to provide further
details about the cause and location of the error.
Reaction: PLC Stop
Remedy: Report this error to Siemens along with the type number.
Check cause of error in the software part named at the line number given.
Program Con-
tinuation:
Switch control OFF - ON.
400004 Code error: [String] Network [No.]
Definitions: [String] : internal error code, module type
[No.] : network number
The user program contains an operation which is not supported by the control unit.
Reaction: PLC Stop
Remedy: Modify and reload user program.
Program Con-
tinuation:
Switch control OFF - ON.
400005 Switch On menu in PLC stop position
Definitions: User program is not being processed
Reaction: Alarm display.
Remedy: Switch controller off/on
Program Con-
tinuation:
Switch control OFF - ON.
400006 Loss of remanent PLC data
Definitions: The following causes are possible:
Control handling (e.g. standard PLC deletion, power up with default values)
Control handling of power up with backed up data without backing up data in advance
Support time exceeded
Reaction: Alarm display.
Remedy: Update the data required.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
400007 Operand error: [String] network [No.]
Definitions: [String] : Module type
[No.] : network number
Reaction: PLC Stop
Remedy: The variable displayed must be checked in the user program for violation of the address range, imper-
missible data type and alignment errors.
Program Con-
tinuation:
Switch control OFF - ON.