Profibus alarms
06/2007 Overview of alarms
2-335
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007 Edition
If no inconsistencies can be found in the parameters, compare the machine data with the configuration
in SDB. In particular, check that the lengths configured for the individual slots do not result in area
overlaps. When you find the cause of the error, change the machine data and/or SDB.
Program Con-
tinuation:
Switch control OFF - ON.
380060 Profibus-DP: alarm %1 on logical address %2 from unassigned station
Parameters: %1 = alarm class
%2 = logical address
Definitions: SDB contains a slave which is not assigned in the NC via the MD parameters (see the help for alarm
380 050/51). The slave is also connected to the PROFIBUS DP. An alarm has been triggered by a
slave of this type.
Alarm class:
01 = Station return (or arrival)
02 = Station failure
Operation with the NC is not possible.
Reaction: Alarm display.
Remedy: Add MD or
change SDB or
disconnect the slave from PROFIBUS DP or
-acknowledge alarm
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
380070 Profibus DP: no input slot available for base address %1 (length %2)
Parameters: %1 = logical base address of area requested
%2 = size of area in bytes
Definitions: An incorrect logical base address was specified for a digital input.
Either no slot has been configured for this base address or the requested area extends beyond the
end of the slot.
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Check your hardware configuration for modules that are not connected or are defective and replace
them.
If the error cannot be eliminated, please make a note of the error text and contact the control system
manufacturer.
Program Con-
tinuation:
Switch control OFF - ON.
380071 Profibus DP: no output slot available for base address %1 (size %2)
Parameters: %1 = logical base address of area requested
%2 = size of area in bytes
Definitions: An incorrect logical base address was specified for a digital or analog input.
Either no slot has been configured for this base address or the requested area extends beyond the
end of the slot.
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Check your hardware configuration for modules that are not connected or are defective and replace
them.
If the error cannot be eliminated, please make a note of the error text and contact the control system
manufacturer.
Program Con-
tinuation:
Switch control OFF - ON.
380072 Profibus DP: output slot for base address %1 (size %2) not allowed
Parameters: %1 = logical base address of area requested
%2 = size of area in bytes