NCK alarms/ISO alarms
06/2007 Overview of alarms
2-21
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
4045 Channel %1 conflict between machine data %2 and machine data %3
Parameters:
Definitions: Using the specified machine data %1 leads to a conflict with machine data %2.
Reaction: NC not ready.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Correct the specified machine data.
Program Con-
tinuation:
Switch control OFF - ON.
4050 NC code identifier %1 cannot be reconfigured to %2
Parameters: %1 = String: Old identifier
%2 = String: New identifier
Definitions: Renaming of an NC code was not possible for one of the following reasons:
The old identifier does not exist
The new identifier is within another type range.
NC codes/vocabulary words can be reconfigured per machine data as long as you stay within the type
range.
Type 1: "true" G codes:G02, G17, G33, G64, ...
Type 2: named G codes:CIP, TRANS, ...
Type 3: addresses which can be set:X, Y, I, J, K, MEAS
Reaction: NC not ready.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department.
Correct MD 10712 NC_USER_CODE_CONF_NAME_TAB (protection level 1).
The list must be built up as follows:
Even address:Identifier to be modified
Following odd address:New identifier
E.g.:NC_USER_CODE_CONF_NAME_TAB[10] = "ROT"
NC_USER_CODE_CONF_NAME_TAB [11] = " "
deletes the function ROT from the control
Program Con-
tinuation:
Switch control OFF - ON.
4060 Standard machine data loaded (%1, %2)
Parameters:
Definitions: Startup with defaults values by means of:
Operation (e.g. commissioning switch)
MD 11200 INIT_MD
Loss of remanent data
Startup operation with backup data, without saving current data
Reaction: Alarm display.
Remedy: After automatically loading the standard MDs, the individual MDs must be entered/loaded in the rele-
vant system.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
4062 Backup data loaded
Definitions: The user data saved in the flash memory are loaded to the SRAM.
Reaction: Alarm display.
Remedy: Load specific machine data again.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program