Operating
7.3 Optimizing the controller data
SIPART PS2 with and without HART communications
98 Operating Instructions, 09/2007, A5E00074631-07
Note
The "Automatic" and "Manual" modes remain set when switching to the "Diagnostics"
mode. The positioner responds as per the set mode:
The predefined setpoint is used as a control variable in the automatic mode.
The last reached position is retained in the manual mode.
See also
Commissioning (Page 107)
Overview parameters A to P (Page 135)
Overview of diagnostics values (Page 179)
Meaning of diagnostics values (Page 181)
7.3 Optimizing the controller data
Note
Initialize the positioner automatically before changing the parameter settings as per your
specific requirements.
The positioner determines the data for control quality automatically during the initialization
process.
The data determined is optimized for a short transient time in case of minor overshoots.
The adjustment can be accelerated or the attenuation can be intensified by optimizing the
data.
The following special cases are ideal examples for a targeted data optimization:
Small actuators with actuating times < 1 s.
Operation with boosters.
You must change the setting of the following parameters to optimize the controller data.
Proceed as follows:
1. Select the parameters in the diagnostics menu.
2. Activate the setting function. Press the increment button
or decrement button for at
least 5 seconds.
3. When you change the selected parameter, it is immediately updated. The effects on the
controller results can then be tested.
22 lmpulse length up / 23 lmpulse length down
You can use these parameters to determine the smallest impulse lengths for each actuating
direction. The actuator is then moved with these lengths. The optimum value depends on the
volume of the actuator in particular. Small values lead to small controller increments and
Vista de pagina 97