Functional safety
8.2 Device-specific safety notes
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
105
8.2.3 Settings
After assembly and commissioning, the following parameter settings should be made for the
safety function:
Safety parameters
Parameter
name
Function Set parameter value Meaning
2.YAGL Rated angle of rotation
of the feedback shaft
33° or 90° to match the
setting for the transmission
ratio selector
Adaptation to the
mechanically set range of
stroke / rotation angle
6.SCUR Current range of
setpoint
4 MA 4...20 mA
riSE Rising -
for actuators with safety
position down/closed (valve
closed)
7.SDIR Setpoint direction
FALL Falling -
for actuators with safety
position up/open (valve
open)
12.SFCT Setpoint function Everything except "FrEE"
linear
constant percentage
inverse constant
percentage
do Depressurizing -
for actuators with safety
position down/closed (valve
closed)
39.YCLS Controller output
tightening
uP Depressurizing -
for actuators with safety
position up/open (valve
open)
Protection against configuration changes
After configuration, the SIPART PS2 positioner must be switched to automatic operation.
You should then fit the housing cover so that the device is protected against unwanted and
unauthorized changes/operation.
The SIPART PS2 positioner is fitted with an additional protective function to prevent
configuration changes:
1. Configure the parameter 43.BIN1 = bLoc2.
2. Bridge terminals 9 and 10 of the binary input BE1.
In this condition, the "configuration" operating level using the keys and HART
communication and manual operation are blocked.