Siemens SIPART PS2 6DR50xx Instrucciones de operaciones Pagina 145

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 242
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 144
Parameterizing/addressing
10.4 Description of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
145
In the other discrete settings, the fixed value for the dead zone is edited.
The factory setting is "Auto".
10.4.2.7 Description of parameters 35 and 36
35.YA - Start of the manipulated variable limit
The factory setting is "0".
and
36.YE - End of the manipulated variable limit
These parameters are used to limit the mechanical actuator travel from stop to stop to the
configured values. This allows the mechanical positioning range of the actuator to be limited
to the effective flow, preventing integral saturation of the controlling closed-loop controller.
See figure in
Description of parameters 37 (Page 145).
Note
"YE" must always be set larger than "YA".
The factory setting is "100".
10.4.2.8 Description of parameters 37
37.YNRM - Normalization of manipulated variable
Using the "YA" and "YE" parameters, you can limit the manipulated variable. This limitation
causes two different scaling types, MPOS or FLOW, for the digital display and for the
position feedback through the current output. See the figure below.
The MPOS scaling type shows the mechanical position from 0 to 100% between the hard
stops of the initialization. The position is not influenced by the "YA" or "YE" parameters. The
parameters "YA" and "YE" are shown in the MPOS scale.
The FLOW scale is a scaling from 0 to 100% over the range between the "YA" and "YE"
parameters. Over this range, the setpoint w is also always 0 to 100%. This results in a more
or less flow-proportional display and position feedback "I
Y
". The flow-proportional display and
position feedback "I
Y
" also results from the use of valve characteristics.
In order to calculate the regulation difference, the setpoint in the digital display is also shown
to the corresponding scale.
The following uses the example of an 80-mm linear actuator to illustrate the dependence of
the stroke on the scaling as well as the parameters "YA" and "YE".
Vista de pagina 144