Alarm, error, and system messages
11.3 Online diagnostics
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
187
11.2.4 Meaning of diagnostic value 53
53 mA - setpoint current
Here, you can display the current setpoint in mA.
Note
All diagnostic value are updated every 15 minutes to a non-volatile memory, so that in case
of a power failure only the values from the last quarter hour will be lost.
11.3 Online diagnostics
11.3.1 Overview of online diagnostics
During operation of the positioner, a few important values and parameters are continually
monitored. In configuration mode, you can configure that monitoring so that the fault
message output will be activated if, for instance, a limit is exceeded.
Information about what events can activate the fault message output can be found in the
table in Chapter
Overview of error codes (Page 188).
This chapter contains particular information about the following situations:
● Possible causes of the fault message.
● Events which activate the fault message output or alarm outputs.
● Settings of parameters needed for event monitoring.
● Cancelling a fault message
In automatic and manual mode, when the fault message output triggers the digital display
shows what fault triggered the message. The two digits on the lower left show the
corresponding error code. If multiple triggers occur at the same time, they are displayed one
after the other cyclically. The device status, including all fault messages, can be called up
using command "#48" over HART.
See also
Overview of error codes (Page 188)
Description of parameters 51 (Page 152)