SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
173
Alarm, error, and system messages
11
11.1 Representation of system messages in the digital display
11.1.1 System messages before initialization
Remarks about the tables:
nn stands for variable numeric values
Error symbol
/ (Slash): texts to the left and the right of the slash blink alternately
Messages before initialization (first commissioning)
Line Message
Up Down
Meaning / cause Measure
CPUStart X
X
Message after connecting the electrical
auxiliary power supply
• Wait
Pnnn.n X Potentiometer voltage of a non-initialized
positioner (P-manual mode) (actual position
value in % of the measuring range)
• Check whether the entire actuator travel
can be covered using the "+" and "-"
buttons and "P---" is never displayed
• Execute the initialization process
P--- X Measuring range was exceeded, the
potentiometer is in the inactive zone, the
transmission ratio selectors or the effective
lever arm are not adjusted as per the
actuator travel
• Switch the transmission ratio selector to
90° especially in case of part-turn
actuators
• Adjust the effective lever length of linear
actuators as per the measuring range
NOINI X Positioner is not initialized
• Start the initialization process
See also
Digital display (Page 91)