Parameterizing/addressing
10.4 Description of parameters
SIPART PS2 with and without HART communications
140 Operating Instructions, 09/2007, A5E00074631-07
Note
Matching the angles
Ensure that the values set in the transmission ratio selector and the "2.YAGL" parameter
match. If not, the value shown on the digital display does not match the actual position.
The factory setting is "33°".
See also
Overview of device components (Page 23)
10.4.1.2 Description of parameters 3 to 5
3.YWAY - display of the range of stroke
Use this parameter to set the value for the real range of stroke. This parameter is optional.
You must set this parameter only if the determined value in mm is to be displayed at the end
of the initialization process of a linear actuator.
Determine the value for the range of stroke as follows:
Fix the carrier pin on the lever at the desired position. This position on the lever has a
specific scaled value, e.g. 25. Set this scaled value in the "YWAY" parameter.
If you select the "OFF" parameter value, the real stroke is not displayed after initialization.
Note
The value set in the "YWAY" parameter must match with the mechanical range of stroke. Set
the carrier to the value of the actuator stroke. If the actuator stroke is not scaled, set it to the
next higher scaled value.
The factory setting is "OFF".
4.INITA - automatic initialization
Use this parameter to start the automatic initialization process. Select the "Strt" parameter
value. Then press the
increment button for at least five seconds. The sequence of the
initialization process from "RUN1" to "RUN5" is displayed on the lower line on the digital
display.
The factory setting is "NOINI".
5.INITM - manual initialization
Use this parameter to start the manual initialization process. Select the "Strt" parameter
value. Then press the
increment button for at least five seconds.