Alarm, error, and system messages
11.4 Fault correction
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
193
11.4 Fault correction
11.4.1 Fault identification
Diagnostics guide
Fault See fault table
In which mode does a fault occur?
Initialization
1
Manual and automatic modes
2 3 4 5
In which environment and under which boundary conditions does a fault occur?
Wet environment (e.g. strong rain or constant condensation)
2
Vibrating (oscillating) control valves
2 5
Impact or shock loads (e.g. vapor shocks or breakaway valves)
5
Moist (wet) compressed air
2
Dirty (contaminated with solid particles) compressed air
2 3
When does a fault occur?
Regularly (reproducible)
1 2 3 4
Sporadically (not reproducible)
5
Mostly after a specific operation time
2 3 5
See also
Remedial measures table 1 (Page 193)
Remedial measures table 2 (Page 195)
Remedial measures table 3 (Page 196)
Corrective measures Table 4 (Page 196)
Remedial measures table 5 (Page 197)
11.4.2 Remedial measures table 1
Fault profile (symptoms) Possible cause(s) Remedial measures
Positioner remains in "RUN 1". Initialization started from the end
position and
The response time of a maximum of
1 minute was not observed.
Network pressure not connected or
it is too low.
A waiting time of up to 1 minute is
essential.
Do not start initialization from the
end position.
Provide the network pressure.