
Alarm, error, and system messages
11.2 Diagnosis
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
185
28 TEMP - current temperature
Current temperature in the positioner enclosure. The sensor is provided on the electronic
printed circuit board.
The temperature display can be toggled between °C and °F by pressing the decrement
button.
29 TMIN - minimum temperature ("min/max pointer")
30 TMAX - maximum temperature ("min/max pointer")
The minimum and maximum temperatures inside the enclosure are continuously determined
and saved using a min/max pointer. They can be reset only in the factory.
31 T1 ... 39 T9 - number of operating hours in temperature ranges T1 to T9
Statistics about the duration of operation in different temperature ranges is maintained in the
device. An average of the measured temperature is taken every hour and the counter
assigned to the corresponding temperature range is incremented. This helps in drawing
conclusions about the past operating conditions of the device and the entire control valve.
The temperature ranges are classified as follows:
T1 T2 T3 T4 T5 T6 T7 T8 T9
Temperature range [°C] - ≥ -30 ≥ -15 ≥ 0 ≥ 15 ≥ 30 ≥ 45 ≥ 60 ≥ 75
≥ -30 < -15 < 0 < 15 < 30 < 45 < 60 < 75 -
Operating hours in temperature ranges T1 to T2
40 VENT1 - number of switching cycles of pilot valve 1
41 VENT2 - number of switching cycles of pilot valve 2
Both these counters sum up the control processes of pilot valves and are used to assess the
switching frequency.
42 STORE - save maintenance data
A save function can be initiated by pressing the increment button for at least 5 seconds.
The diagnostics data 7 to 18 is saved in the non-volatile memory as "data of last
maintenance". This diagnostics data contains selected values whose changes can give
information about mechanical wear and tear of the valve.
This function is normally operated through the PDM, menu command "Device-> Save
maintenance info". The data of the last maintenance data can be compared with the current
data using the PDM.
43 PRUP - prediction up
and
Comentarios a estos manuales