Commissioning
9.3 Commissioning part-turn actuators
SIPART PS2 with and without HART communications
124 Operating Instructions, 09/2007, A5E00074631-07
2. Set the "YFCT" parameter to "turn". Press the decrement button for this purpose. The
following is shown on the digital display:
3. Call the second parameter "YAGL". Press the
operating mode button for a short while
for this purpose. The following is shown on the digital display:
4. Call the "INITM" parameter. Press the
operating mode button twice for this purpose.
The following is shown on the digital display:
5. Start the initialization process. Press the increment button
for at least 5 seconds until
the digital display shows the following:
6. The current potentiometer position is shown on the digital display after 5 seconds.
Examples of the displayed potentiometer positions are given below:
7. Determine the end position 1 of the actuator.
8. Move the actuator spindle to the desired position by pressing the increment or
decrement buttons.
9. Accept the current position by pressing the
operating mode button. The following is
shown on the digital display: