Commissioning
9.3 Commissioning part-turn actuators
SIPART PS2 with and without HART communications
120 Operating Instructions, 09/2007, A5E00074631-07
11. The following display indicates that the initialization has been completed successfully:
Note
If the "YWAY" parameter has been set, the digital display shows the total stroke in mm.
Aborting the manual initialization process
1. Press the operating mode button. The digital display shows the "INITM" parameter.
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the operating mode button
for at least
5 seconds.
3. The software status is displayed.
4. After releasing the
operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.
9.3 Commissioning part-turn actuators
9.3.1 Preparing part-turn actuators for commissioning
NOTICE
Setting of the adjustment angle
The usual adjustment angle for part-turn actuators is 90°. Accordingly set the transmission
ratio selector in the positioner to 90°.
Condition
The following conditions must be fulfilled before activating the initialization:
1. You have installed the positioner for the part-turn actuators using the suitable mounting
kit.
2. You have connected the actuator and the positioner to the pneumatic lines.
3. Pneumatic auxiliary power is supplied to the positioner.
4. The positioner has been connected to a suitable current or voltage source.