Alarm, error, and system messages
11.4 Fault correction
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
197
Symptoms Possible cause(s) Corrective measures
• Positioner doesn't move control
valve to the stop (at 20 mA).
• Supply pressure too low. Load on
the feeding controller or system
output is too low.
• Increase supply pressure, insert ballast
converter
• Select 3/4-wire mode
Error table 4
See also
Service and maintenance (Page 199)
11.4.6 Remedial measures table 5
Fault profile (symptoms) Possible cause(s) Remedial measures
• Zero point displaces
sporadically (> 3%).
• Impact or shock loads result in
accelerations so high that the friction clutch
moves, e.g. due to "vapor shocks" in vapor
lines.
• Rectify the causes for shock
loads.
• Re-initialize the positioner.
• Electrical auxiliary power supply is not
adequate.
• Check the electrical auxiliary
power supply.
• The device function has
completely failed: no view even
on the digital display.
• In case of very high continuous loads due to
vibrations (oscillations):
• Screws of the electrical connecting
terminals may be loosened.
• Electrical connecting terminals and/or
electronic components may be knocked out.
• Tighten the screws firmly and
secure using sealing wax.
• Repair
1)
• For prevention: Install the
positioner on the damping
pads.
Fault table 5
1)
More information is given under the also-see link.
See also
Service and maintenance (Page 199)