Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
133
Parameter Function Parameter values Unit
Setpoint function
Linear Lin
1 : 25 1 - 25
1 : 33 1 - 33
Equal percentage
1 : 50 1 - 50
25 : 1 n1 - 25
33 : 1 n1 - 33
Inverse equal percentage
50 : 1 n1 - 50
12.SFCT
Freely adjustable FrEE
13.SL0 ...
33.SL20 1)
Setpoint turning point
13.SL0 0 %
14.SL1 .... 5 % ...
32.SL19 95 %
33.SL20
at
100 %
0.0 ... 100.0
34.DEBA Dead zone of closed-loop controller Auto / 0.1 ... 10.0
35.YA Start of the manipulated variable limit 0.0 ... 100.0
36.YE End of the manipulated variable limit 0.0 ... 100.0
Manipulated variable scaling
Mechanical MPOS
37.YNRM
On flow FLOW
Manipulated variable direction of action for display and position feedback
Rising riSE
38.YDIR
Falling FALL
Manipulated variable tight closing
None no
Top only uP
Bottom only do
39.YCLS
Top and bottom uP do
40.YCDO Lower value for tight closing 0.0 ... 0.5 ... 100 %
41.YCUP Upper value for tight closing 0.0 ... 99.5 ... 100 %
Function of BE1 Normally open Normally closed
None OFF
Message only on -on
Block configuration bloc1
Block configuration and manual bloc2
Move valve to position YE uP -uP
Move valve to position YA doWn -doWn
Block movement StoP -StoP
42.BIN1 2)
Partial-Stroke-Test PST -PST
Vista de pagina 132