I
y
module Without explosion
protection (also EEx d)
With EEx ia/ib explosion
protection
With EEx n explosion
protection
6DR4004-8J (without
explosion protection)
6DR4004-6J 6DR4004-6J
Direct current output for position
feedback
2-wire connection 2-wire connection 2-wire connection
Nominal signal range i 4 ... 20 mA, short circuit
resistant
4 ... 20 mA, short circuit
resistant
4 ... 20 mA, short circuit
resistant
Dynamic range 3.6 ... 20.5 mA 3,6 ... 20.5 mA 3.6 ... 20.5 mA
Auxiliary voltage U
H
+12...+35 V +12...+30 V +12 ... +30 V
External load R
B
[kΩ] (U
H
[V] - 12 V) /i [mA] (U
H
[V] - 12 V) /i [mA] (U
H
[V] - 12 V) /i [mA]
Transmission fault ≤ 0.3% ≤ 0,3 % ≤ 0.3%
Temperature effect ≤ 0.1%/10 K
(≤ 0.1%/18°F)
≤ 0.1%/10 K
(≤ 0.1%/18°F)
≤ 0.1%/10 K
(≤ 0.1%/18°F)
Resolution ≤ 0,1 % ≤ 0,1 % ≤ 0.1%
Residual ripple ≤ 1 % ≤ 1 % ≤ 1 %
Internal capacitance C
i
- ≤ 11 nF -
Internal inductance L
i
- Negligible -
For connecting to circuits with Intrinsically safe:
U
i
≤ 30 V DC
I
k
≤ 100 mA
P
i
≤ 1 W (only T4)
U
i
≤ 30 V DC
I
k
≤ 100 mA
P
i
≤ 1 W (only T4)
Electrical isolation Galvanically isolated from
the standard controller
Galvanically isolated from
the standard controller
Galvanically isolated from
the standard controller
Test voltage 840 V DC, 1 s 840 V DC, 1 s 840 V DC, 1 s
Non-contacting position sensor (not
for EEx d version)
Without explosion
protection (also EEx d)
With EEx ia/ib explosion
protection
With EEx n explosion
protection
Actuating range
• Linear actuator
3 ... 130 mm (0.12 ...
5.12"), up to 200 mm
(7.87") on request
3 ... 130 mm (0.12 ...
5.12"), up to 200 mm
(7.87") on request
3 ... 130 mm (0.12 ...
5.12"), up to 200 mm
(7.87") on request
• Part-turn actuator
30° ... 100° 30° ... 100° 30° ... 100°
Linearity (as per correction through
SIPART PS2)
• Linear actuator
± 1% ± 1% ± 1%
• Part-turn actuator
± 1% ± 1% ± 1%
Hysteresis ± 0.2% ± 0.2% ± 0.2%
Continuous operating temperature -40°C ... +85°C
(-40°F ... +185°F),
extended temperature
range on request
-40°C ... +85°C
(-40°F ... +185°F),
extended temperature
range on request
-40°C ... +85°C
(-40°F ... +185°F),
extended temperature
range on request
IP-ingress protecting IP68/NEMA 4X IP68/NEMA 4X IP68/NEMA 4X