Commissioning
9.2 Commissioning linear actuators
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
117
7. The following display indicates that the automatic initialization is complete:
Setting parameter 3
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter to the read value. Use the
increment or decrement buttons for
this purpose.
Aborting the automatic initialization process
1. Press the operating mode button. The following is shown on the digital display:
2. Exit the "Configuration" mode. To do this, press the operating mode button
for at least
5 seconds.
3. The software status is displayed.
4. After releasing the
operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.
See also
Sequence of automatic initialization (Page 108)
9.2.3 Manual initialization of linear actuators
You can use this function to initialize the positioner without needing to move the actuator to
the end stops. The start and end positions of the actuator travel are set manually. When the
control parameters are optimized, the further initialization process runs automatically.
Conditions
The following conditions must be fulfilled before activating the manual initialization:
1. The positioner has been prepared for using on linear actuators.
2. The actuator spindle can be moved completely.
3. The displayed potentiometer position is within the permissible range between "P5.0" and
"P95.0".